RTE France

ADNSecurityAnalysisParameters

The ADNSecurityAnalysisParameters is an extension of the SecurityAnalysisParameters class that provides specific configuration for the security analysis mode of Hades. Read this documentation page to learn more about security analysis generic parameters. Read this documentation page to learn more about the Hades load-flow configuration.

Optional properties

afterContingencyBalanceEpsilon

The afterContingencyBalanceEpsilon property is an optional property that defines the maximum value accepted for the unbalance at the slack node in contingency simulation. The default value for this parameter is -1.

constraints

The contraints property is an optional property that defines if violations should be computed. The default value for this parameter is true.

fastMode

The fastMode property is an optional property that disable some features to improve performance. In practice, if this parameter is set to true, the maximal number of allowed PV-PQ switches is set to 0. The default value for this parameter is false.

flowConstraintReference

The flowConstraintReference property is an optional property that defines the current limits (permanent or temporary) to use as reference for relative variation criteria. The default value for this parameter is 0.

minPowerTransferRatio

The minPowerTransferRatio property is an optional property that defines the threshold of lost MW caused by a contingency to run a simulation for this contingency. The default value for this parameter is 3.

minVMaxV

The minVMaxV property is an optional property that defines if the minimum and maximum voltage per substations for all contingencies should be computed. The default value for this parameter is false.

powerTransferRatio

The powerTransferRatio property is an optional property that defines if the power transfer coefficients should be computed. The default value for this parameter is false.

worsenedFlowConstraintsDelta

The worsenedFlowConstraintsDelta property is an optional property that defines the worsening delta for CURRENT violations. The default value for this parameter is -1.

worsenedFlowConstraintsThreshold

The worsenedFlowConstraintsThreshold property is an optional property that defines the worsening threshold for CURRENT violations. The default value for this parameter is 0.1.

worsenedHighVoltageConstraintsDelta

The worsenedHighVoltageConstraintsDelta property is an optional property that defines the worsening delta for HIGH_VOLTAGE violations. The default value for this parameter is -1.

worsenedHighVoltageConstraintsThreshold

The worsenedHighVoltageConstraintsThreshold property is an optional property that defines the worsening threshold for HIGH_VOLTAGE violations. The default value for this parameter is -1.

worsenedLowVoltageConstraintsDelta

The worsenedLowVoltageConstraintsDelta property is an optional property that defines the worsening delta for LOW_VOLTAGE violations. The default value for this parameter is -1.

worsenedLowVoltageConstraintsThreshold

The worsenedLowVoltageConstraintsThreshold property is an optional property that defines the worsening threshold for LOW_VOLTAGE violations. The default value for this parameter is -1.

writeNState

The writeNState property is an optional property that defines if the pre-contingency results should be exported. The default value for this parameter is true.

Example

This is an example of a security analysis parameters file with the ADNSecurityAnalysisParameters extension:

{
  "version" : "1.0",
  "load-flow-parameters" : {
    ...
  },
  "extensions" : {
    "ADNSecurityAnalysisParameters": {
      "afterContingencyBalanceEpsilon": 1.0,
      "constraints": true,
      "fastMode": true,
      "flowConstraintReference": 0,
      "minPowerTransferRatio": 3,
      "minVMaxV": true,
      "powerTransferRatio": true,
      "worsenedHighVoltageConstraintsDelta": 4.0,
      "worsenedHighVoltageConstraintsThreshold": 0.1,
      "worsenedLowVoltageConstraintsDelta": 5.0,
      "worsenedLowVoltageConstraintsThreshold": 0.1,
      "worsenedFlowConstraintsDelta": -1,
      "worsenedFlowConstraintsThreshold": 0.1,
      "writeNState": true
    }
  }
}